3,105 bytes added
, 18:33, 21 April 2012
'''All of these plugins are dependant upon the successful installation of apcupsd prior to their use.'''
=== apcups_battery ===
This plugin reports the APC UPS battery statistics. The plugin should be saved with a filename 'apcups_battery' and a link can then be generated in the munin plugins directory:
ln -s /path/apcups_battery /etc/munin/plugins/apcups_battery
#!/bin/sh
#
# Plugin to report APC Battery statistics. Relies on apcupsd package being installed.
#
# Contributed by Tim Chappell
#
# Magic markers - optional - used by installation scripts and
# munin-config:
#
#%# family=manual
#%# capabilities=autoconf
SRCFILE=/var/log/apcupsd.status
if [ "$1" = "config" ]; then
echo 'graph_category power'
echo 'graph_title UPS Battery Stats'
echo 'graph_vlabel Battery condition'
echo 'apc_ups_battery_volts.label Battery (V)'
echo 'apc_ups_battery_volts.draw LINE1'
echo 'apc_ups_battery_charge.label Battery Charge (%)'
echo 'apc_ups_battery_charge.draw LINE1'
echo 'apc_ups_battery_temp.label Battery Temp (degC)'
echo 'apc_ups_battery_temp.draw LINE1'
echo 'apc_ups_battery_rtr.label Battery Runtime (mins)'
echo 'apc_ups_battery_rtr.draw LINE1'
exit 0
fi
/bin/cat $SRCFILE | /usr/bin/awk '{if ($1=="BATTV") {printf "apc_ups_battery_volts.value %s\n",$3}}'
/bin/cat $SRCFILE | /usr/bin/awk '{if ($1=="BCHARGE") {printf "apc_ups_battery_charge.value %s\n",$3}}'
/bin/cat $SRCFILE | /usr/bin/awk '{if ($1=="ITEMP") {printf "apc_ups_battery_temp.value %s\n",$3}}'
/bin/cat $SRCFILE | /usr/bin/awk '{if ($1=="TIMELEFT") {printf "apc_ups_battery_rtr.value %s\n",$3}}'
=== apcups_power ===
This plugin reports the APC UPS power consumption and running costs. The plugin should be saved with a filename 'apcups_power' and a link can then be generated in the munin plugins directory:
ln -s /path/apcups_power /etc/munin/plugins/apcups_power
Edit the '''COST''' variable as appropriate - it determines the cost of each kWh (set to pence or cents as required).
#!/bin/sh
#
# Plugin to report APC UPS power and monthly running cost.
#
# Contributed by Tim Chappell
#
# Magic markers - optional - used by installation scripts and
# munin-config:
#
#%# family=manual
#%# capabilities=autoconf
# Cost (pence) per kWh
COST=11
SRCFILE=/var/log/apcupsd.status
if [ "$1" = "config" ]; then
echo 'graph_category power'
echo 'graph_title UPS Power Consumption'
echo 'graph_vlabel Watts'
echo 'apc_ups_power.label Consumed Power'
echo 'apc_ups_power.draw LINE1'
echo 'running_cost.label Monthly running cost'
echo 'running_cost.draw LINE1'
exit 0
fi
NOMPOWER=`awk '{if($1=="NOMPOWER"){print $3}}' $SRCFILE`
awk -vc=$COST -vp=$NOMPOWER '{if($1=="LOADPCT"){printf"apc_ups_power.value %d\n",($3/100*p)}}' $SRCFILE
awk -vc=$COST -vp=$NOMPOWER '{if($1=="LOADPCT"){printf"running_cost.value %.2f\n",((($3/100*p)/1000)*24*30*c/100)}}' $SRCFILE
----